LLM workflow: one prompt, export JSON, rules, and validated import

This page describes a single upload workflow for mechanical engineers: send the canonical prompt, the data-model export JSON, and fault/rule context (strongly recommended) to an LLM; get back import-ready JSON; validate it so you know it will parse on the Open-FDD backend; then PUT /data-model/import and run FDD (or Sparkl/tests) as needed.

Best practice: Decide which Open-FDD faults and rules you will run before finalizing polling. The canonical prompt is fault-first: it tells the model to gather job context (faults, YAML, units, production vs bench, weather scope) or to stay conservative on polling until that context exists.

Automated path available: External OpenAI-compatible agents (for example Open‑Claw) can automate the same flow by calling GET /data-model/export, fetching platform documentation context from GET /model-context/docs, and then calling PUT /data-model/import with validated import JSON. The manual copy-paste workflow below always works too.

Web-connected agents: If your LLM can fetch HTTPS documentation, point it at the published Data modeling hub and this page’s template anchor Copy/paste prompt template (recommended) in addition to (or alongside) GET /model-context/docs, so instructions stay aligned with the live docs site.

Full AFDD stack vs column-map resolvers: This workflow still targets Brick point classes (brick_type), rule_input, and related import fields because rule YAML on the platform uses Brick-class logical names. In fdd-loop, the default BrickTtlColumnMapResolver builds column_map from config/data_model.ttl (same semantic model you enrich with import JSON). The LLM does not emit a separate “ontology manifest” for PyPI-style ManifestColumnMapResolver—that path is for library / custom pipelines (Engine-only deployment and external IoT pipelines, column map resolver workshop). If you ever run the loop with a manifest-only resolver, keep rule YAML and brick_type aligned with whatever logical keys your rules use.


What you upload to the LLM

  1. The canonical prompt — Use AI-assisted data modeling (section LLM prompt and agent guidelines), the inline template below on this page (“Copy/paste prompt template”), or the Technical reference — LLM tagging workflow. You can copy from this page or keep an optional local mirror (e.g. pdf/canonical_llm_prompt.txt) for agents. The prompt must tell the LLM to return only {"points": [...], "equipment": [...]} with Brick types, rule_input slugs, equipment_name, feeds/fed_by, polling, and units (subject to the pre-flight / job context rules in the template).

  2. The export JSON — From GET /data-model/export (optionally ?site_id=YourSiteName). Each row includes point fields (point_id, bacnet_device_id, object_identifier, object_name, external_id, site_id, site_name, equipment_id, equipment_name, brick_type, rule_input, unit, polling, …). Rows may also include engineering (and equipment_metadata) — a per-equipment mirror from the DB so the LLM sees rated/submittal context next to points. On import, write engineering updates under equipment[].engineering, not as ad-hoc point fields (see Data model engineering and examples/223P_engineering/). Unimported BACnet rows have point_id: null and null tagging fields until you import.

  3. Faults and rules for this job (strongly recommended) — So the LLM can align rule_input, Brick types, units, and especially polling with what you will actually run in Open-FDD:

    • Paste YAML from your project’s rules (e.g. from stack/rules/ or your own rule files). This is the best input for correct polling decisions — the model can see exactly which point inputs each rule uses.
    • Or point the LLM at the Fault rules overview and Expression Rule Cookbook (AHU, chiller, weather, advanced recipes) and list which fault IDs or recipes apply.

Polling and YAML: Without fault/rule context, many BACnet points may be tagged correctly but should still stay polling: false. The canonical prompt defaults to asking for job context first or emitting a conservative draft (mostly polling: false) until you provide which faults run and ideally the actual rule YAML for the job.


Use this as your LLM system or developer prompt when transforming GET /data-model/export into import JSON. This is the canonical copy-paste text for the published docs (save to a local file such as pdf/canonical_llm_prompt.txt if you want a path for agents or runbooks).

You are transforming Open-FDD export JSON into Open-FDD import JSON.

I will paste JSON from:
GET /data-model/export?site_id=<site_id>

Your job is to return ONLY valid JSON with EXACTLY these two top-level keys:

{
  "points": [...],
  "equipment": [...]
}

Do not return markdown.
Do not return explanations.
Do not return comments.
Do not return any extra top-level keys.

Exception for multi-turn chat: if fault/rule job context is still missing and you must ask pre-flight questions first, you may reply with plain-language questions only in that turn (see PRE-FLIGHT below). When you emit import JSON, the STRICT OUTPUT REQUIREMENTS at the end apply.

--------------------------------------------------
PRE-FLIGHT / JOB CONTEXT (required before final polling decisions)
--------------------------------------------------

Polling must be driven by the **actual faults and rules** the operator plans to run in Open-FDD — not by “this point looks generally useful.”

Before deciding final polling values, establish job context.

**Required pre-flight question:** What faults/rules are you going to run in Open-FDD?

Ask or confirm the following (plain language) if not already answered:

2. Can you provide the actual YAML rule files or rule snippets for this job?
3. Are units imperial or metric for this job?
4. Is this a production/live HVAC job or a bench/demo/test bench?
5. Do you want weather-related rules or weather polling included?
6. Should polling be limited to points required by the selected faults, or also include extra plotting/trending points the operator explicitly wants?

HARD RULE — if faults/rules context is missing:

- Either (a) ask the pre-flight questions above and wait (no import JSON in that turn), OR (b) return import JSON that is an explicitly **conservative draft**: set polling=false for every point unless it is clearly essential; do **not** enable broad polling coverage by guesswork.
- Do not treat aggressive polling=true choices as “final” until the operator has described which faults run and (ideally) supplied YAML or clear rule snippets.

If YAML rules or snippets **are** provided:

- Align brick_type, rule_input, unit, and polling with those rules’ inputs.
- Set polling=true primarily for points **required** by the selected faults, plus any points the operator **explicitly** approved for plotting/trending.
- Do not turn on polling for unrelated “nice to have” points unless the operator asked for broader trending.

**After faults/rules are known, you must:**

- Infer which **Brick classes** and **rule_input** slugs those rules require (from YAML expressions and the Expression Rule Cookbook when YAML is thin). On the full Open-FDD stack, the engine maps those Brick names to trend/BACnet columns from the published data model (TTL), so keep **brick_type** and **rule_input** consistent with the YAML—not a separate hand-authored column_map in this JSON.
- Set **polling=true** for points that clearly supply those required inputs once tagged.
- Leave **polling=false** for unrelated points unless the operator explicitly asked for broader trending/plotting.

**Example:** If the operator runs only **sensor-bounds** and **sensor-flatline**-style temperature rules, BACnet **commands**, **setpoints**, **occupancy/schedules**, and **unrelated weather/Open-Meteo** points usually stay **polling=false** unless the operator asked to trend them or a named rule truly needs them.

--------------------------------------------------
POINT RULES
--------------------------------------------------

For each point in the input:

1. KEEP every existing field exactly as provided, including:
- point_id
- bacnet_device_id
- object_identifier
- object_name
- external_id
- site_id
- site_name
- equipment_id
- any other existing point fields present in the export

Note: the export may include **engineering** / **equipment_metadata** on each row (a mirror of **equipment**-level metadata). For **PUT /data-model/import**, rated/submittal engineering belongs under **equipment[].engineering** (see EQUIPMENT RULES). Do not add spurious extra keys on point objects if your validator rejects them; fold engineering into the **equipment** array once per **equipment_name** + **site_id**.

2. ADD or FILL these fields:
- brick_type (Brick **point** class — sensor, command, setpoint, …)
- rule_input
- polling
- unit
- equipment_name
- equipment_type (Brick **equipment** class — see §4 — powers Data Model Testing summary buttons)

3. brick_type:
Choose the best matching Brick class for the point.
Use a standard Brick class name such as:
- Supply_Air_Temperature_Sensor
- Return_Air_Temperature_Sensor
- Mixed_Air_Temperature_Sensor
- Zone_Air_Temperature_Sensor
- Damper_Position_Command
- Supply_Air_Flow_Sensor
- Static_Pressure_Sensor
- Occupancy_Command
Prefix with "brick:" only if the input already uses that style consistently. Otherwise omit the prefix.

4. equipment assignment:
Assign points to equipment by NAME ONLY.
Example:
- "equipment_name": "AHU-1"
- "equipment_name": "VAV-1"

Do NOT use equipment_id or any UUID for equipment relationships.

**Conservative equipment_name inference:**
- Set or change **equipment_name** only when **strongly supported** by BACnet **device** grouping, consistent **object_name** / **external_id** patterns, and any operator brief — not from a single ambiguous point name.
- If grouping is unclear, keep the export’s **equipment_name** / **equipment_id** relationship as-is rather than inventing AHUs/VAVs.

**equipment_type (Brick 1.4 equipment class — best LLM guess, human verifies with one click):**
- When you set **equipment_name** on points (or list equipment in **equipment[]**), also set **equipment_type** to the **most specific defensible Brick equipment class** as a **bare local name** (no `brick:` prefix), matching what Open-FDD writes to RDF for `rdf:type`.
- Goal: the operator can open **Data Model Testing → Summarize your HVAC** and use preset buttons (**AHUs**, **VAV boxes**, **Chillers**, **Central plant**, **Meters**, …) without re-tagging. Those queries filter on Brick **1.4** classes such as:
  - **Air_Handling_Unit** — central air handler (supply/return/mixed air, fan, coils context)
  - **Variable_Air_Volume_Box** or **Variable_Air_Volume_Box_With_Reheat** — VAV / fan-powered terminal
  - **Chiller**, **Boiler**, **Cooling_Tower**, **Water_Pump**, **Heat_Exchanger**
  - **Chilled_Water_System**, **Condenser_Water_System**, **Hot_Water_System** — distribution systems when the row truly represents that system
  - **HVAC_Zone** — thermal / zoning context when points are zone-level only
  - **Building_Electrical_Meter** — building-level electrical meter equipment (not every kW sensor)
  - Generic fallback: **Equipment** (Open-FDD default) when class is unclear — better than mis-typing a VAV as a Chiller.
- **Same names as the UI presets** are maintained in **[open-fdd-afdd-stack](https://github.com/bbartling/open-fdd-afdd-stack)** in [`frontend/src/data/brick-1.4-query-class-allowlist.ts`](https://github.com/bbartling/open-fdd-afdd-stack/blob/main/frontend/src/data/brick-1.4-query-class-allowlist.ts) (regression test: [`data-model-testing-queries.brick.test.ts`](https://github.com/bbartling/open-fdd-afdd-stack/blob/main/frontend/src/data/data-model-testing-queries.brick.test.ts)).
- On **equipment[]** rows, include **equipment_type** whenever you include **equipment_name** + **site_id** so created/updated equipment gets the correct type before points attach.

5. unit:
Fill unit when known.
Use standard abbreviations consistent with the job units mode from pre-flight (imperial vs metric):
- temperature -> "degF" or "°F" (imperial) / "degC" or "°C" (metric) as appropriate
- percentage -> "percent" or "%"
- airflow -> "cfm" (imperial) or align with metric job conventions when stated
- binary / boolean -> "0/1"
- power -> "W"
- irradiance -> "W/m²"
Preserve unit strings already present in the export when they are consistent with the stated job mode; do not rewrite known-good values unless the operator asked for conversion.
If unknown, use null.

**Conservative units (power, flow, energy):**
- Do **not** force **unit** for ambiguous power, flow, or energy points (e.g. kW vs W, CFM vs percent of max, BTU vs MBH) without **operator confirmation** or an unambiguous BACnet engineering unit in context.
- Prefer **null** over a confident-looking guess that could mislead FDD and plots.

6. polling:
Set polling=true **primarily** for points required by the **specific faults/rules** the operator intends to run, plus any **operator-approved** plotting/trending points (see pre-flight question 6).
Set polling=false for points not needed by those rules or approved use cases.
Do **not** enable broad polling just because a point looks generally useful.
If fault/rule context has not been provided, follow the HARD RULE in PRE-FLIGHT (conservative draft or ask first).
If YAML or rule snippets were provided, align polling (and brick_type, rule_input, unit) with those rules.

7. rule_input:
Only populate rule_input when it is actually needed for disambiguation or explicit aliasing.

Use rule_input in these cases:
- two or more points in the same equipment or rule scope share the same Brick class
- a rule needs a stable explicit alias that cannot be reliably inferred from Brick class alone
- the point name clearly indicates a meaningful distinction such as pre/post, entering/leaving, heating/cooling, min/max, supply/return when same-class ambiguity exists

Example:
If one AHU has two Supply_Air_Temperature_Sensor points:
- SAT before coil -> rule_input: "sat_pre"
- SAT after coil -> rule_input: "sat_post"

If only one point of that Brick class exists in scope and it is unambiguous, set:
- "rule_input": null

Do NOT invent unnecessary rule_input values for every point.

8. weather / Open-Meteo / network weather points:
Do not invent weather equipment or weather points that are not in the export.
If the export already contains Open-Meteo or other weather/network points, keep those rows in the output. Set polling=true only when weather-related faults/rules are in scope, or the operator explicitly wants weather polling/plotting; otherwise prefer polling=false for weather rows when fault context does not require them.
Do not add new weather points unless the operator or attached rules explicitly require them.

9. fallback behavior:
If uncertain:
- brick_type = null
- rule_input = null
- unit = null
- polling = false
- equipment_type = omit or null (backend defaults to generic Equipment — use this instead of a wrong class)

--------------------------------------------------
REAL-JOB / CONSERVATIVE MODE (not optional for production buildings)
--------------------------------------------------

Bench and demo setups can be forgiving; **on a real live HVAC job** the model must not drift from discoverable truth.

**Do not invent or guess:**

- Extra BACnet devices, synthetic weather stations, or integration “placeholder” equipment
- Equipment rows or feeds/fed_by topology that are not in the export, the user’s brief, or an attached as-built
- Point rows that were not in the export (no hallucinated objects)
- **Engineering** numerics (HP, tons, MBH, design CFM, kW) on **equipment[].engineering** without operator-provided submittal/spec text

**Preserve identity exactly** (character-for-character when the export provides them):

- `bacnet_device_id`, `object_identifier`, `object_name`, `external_id`, `point_id`, `site_id`, `site_name`, `equipment_id`

**When unsure, prefer the safer default:**

- `null` for unknown Brick type or unit — not a best guess
- `polling: false` unless the point is clearly needed for the faults/rules or plotting/trending the operator asked for
- Omit `feeds` / `fed_by` rather than inferring ductwork relationships
- Saying (in a side channel) “cannot determine X from export” is better than fabricating X in JSON

**Demo vs live:** Use pre-flight answers: test-bench convenience must not override the rules above on a production import.

**Operator review before import (short checklist):**

1. Compare row count and key BACnet fields to the latest `GET /data-model/export` — no mystery devices.
2. Confirm every non-null `site_id` is still a UUID from `GET /sites`.
3. `PUT dry-run` is not currently supported by the Open-FDD API for `PUT /data-model/import`; use schema/Pydantic validation first, and if you need a no-risk rehearsal, run the same `PUT` against a staging instance while comparing inputs from `GET /data-model/export` and site UUIDs from `GET /sites`.
4. After import, verify a handful of BACnet reads match the gateway for the same object ids.
5. On **Data Model Testing**, run **AHUs**, **VAV boxes**, **Class summary**, etc., to confirm **equipment_type** choices match reality (quick human QA).

--------------------------------------------------
EQUIPMENT RULES
--------------------------------------------------

Create an "equipment" array with one entry per equipment.

Each equipment item must use this shape:

{
  "equipment_name": "AHU-1",
  "equipment_type": "Air_Handling_Unit",
  "site_id": "<same site_id as the points>",
  "feeds": ["VAV-1"]
}

or

{
  "equipment_name": "VAV-1",
  "equipment_type": "Variable_Air_Volume_Box",
  "site_id": "<same site_id as the points>",
  "fed_by": ["AHU-1"]
}

Rules:
- Use equipment names only
- Do not use equipment UUIDs
- Preserve the exact site_id from the export
- Set **equipment_type** on each row (see §4) so Brick `rdf:type` matches **Data Model Testing** preset queries (Brick **1.4** vocabulary).
- Include feeds/fed_by only when supported by the provided data or clearly specified by the user
- Do not invent mechanical relationships unless they are explicitly given or obvious from the provided context

**Optional — engineering metadata (`equipment[].engineering`):**
- Open-FDD **GET /data-model/export** duplicates **equipment.metadata.engineering** on each point row as **engineering** for LLM context. On import, put updates under **equipment[]** using the same **equipment_name** + **site_id**, with an **engineering** object (nested sections such as **mechanical**, **electrical**, **controls**, **topology**, **documents** — see project examples).
- You **may** help capture **rated** data: design CFM, cooling/heating capacity, fan or pump motor nameplate (HP/kW/FLA), coil or heat-exchanger ratings, feeder/panel references, **when the operator provides submittal, schedule, or as-built values** (or asks you to transcribe pasted specs).
- Do **not** invent numeric ratings (HP, tons, MBH, CFM, kW) from BACnet object names alone.
- Preserve existing **engineering** from the export when present unless the operator asks to correct it.

--------------------------------------------------
STRICT OUTPUT REQUIREMENTS
--------------------------------------------------

When emitting import JSON:
- Return ONLY valid JSON
- EXACTLY two top-level keys: "points" and "equipment"
- No "sites"
- No "relationships"
- No "equipments"
- No prose
- No markdown
- No comments

If duplicate external_id appears for the same site, keep the last occurrence.

Now process the following input JSON:

After the final line, paste the export JSON (or send it as the next user message). This template works for manual copy-paste and external agents (including Open‑Claw workflows).

Again, for agents with web access: Data modeling (GitHub Pages) and this template section.


Where the rules live

What Where
Fault rules overview docs/rules/overview — FDD rule types, YAML format, Brick-driven inputs.
Expression Rule Cookbook docs/expression_rule_cookbook — AHU, chiller, weather, and advanced recipes; rule_input examples and expression patterns.
Actual YAML rule files stack/rules/ in the repo (or your rules_dir). Paste snippets into the LLM session so it uses the same input names and can set polling only where rules need data.

The cookbook is not a fault rule file itself; it’s documentation. The rules you want to use are the YAML files in stack/rules/ (or your project’s rules). For the LLM, prefer pasting that YAML; you can also say “use rule_input slugs from the Expression Rule Cookbook (sat, rat, zone_temp, …)” when YAML is not at hand — but polling decisions will be less certain until you tie them to concrete faults.


Engineering metadata (fan HP, pumps, coils, design CFM, …)

Yes — the export exposes equipment-level engineering on each row as engineering (and raw equipment_metadata). The import accepts the same data on equipment[] via engineering, merged into equipment.metadata.engineering in PostgreSQL and emitted into the knowledge graph (see open_fdd/platform/data_model_ttl.py).

Use this for nameplate / submittal style fields (design CFM, cooling/heating capacity, motor HP or FLA, feeder panel, topology sketches, source drawing references). FDD rules still run on time-series columns from polled points; engineering scalars are for context, SPARQL, dashboards, and downstream analytics unless you extend the runner.

The canonical prompt tells the LLM to only fill or change engineering when the operator supplies evidence — not to invent tons, HP, or CFM from BACnet names alone.


Feeds / fed_by (HVAC topology)

  • feeds — This equipment supplies another (e.g. AHU feeds VAV).
  • fed_by — This equipment is supplied by another (e.g. VAV fed_by AHU).

If topology is not known confidently, omit feeds/fed_by rather than guessing. You can add or refine relationships later.


Validate before import (so backend CRUD accepts it)

The Open-FDD PUT /data-model/import endpoint expects a body that matches the DataModelImportBody Pydantic model: exactly points (array) and optional equipment (array). If the LLM returns extra keys, wrong types, or invalid UUIDs, the API returns 422 Unprocessable Entity.

To avoid that:

  1. Instruct the LLM — In your prompt, add: “Return only valid JSON that conforms to the Open-FDD import schema: top-level keys points and equipment only; each point has the fields listed in the prompt; equipment items use equipment_name, site_id, optional feeds / fed_by, optional engineering / metadata.”

  2. Use the API’s JSON Schema — The OpenAPI spec at GET /openapi.json (or GET /docs and “openapi.json”) includes a schema for the import body. You can:
    • Export that schema (e.g. the DataModelImportBody and nested PointImportRow / EquipmentImportRow from the spec) and give it to the LLM: “Return JSON that validates against this schema.”
    • Or run a local validation step before pasting into the UI: validate the LLM’s JSON against the same schema (e.g. with a small script or tool that loads the schema and runs jsonschema.validate). If it passes, PUT /data-model/import will accept it (aside from referential issues like missing site_id).
  3. Common failure: site_id is not a UUIDPUT /data-model/import expects points[].site_id to be either:
    • a UUID string (as returned by GET /data-model/export), or
    • null/omitted (so the backend can resolve it from points[].site_name).

    If you see an error like: site_id must be a valid UUID from GET /sites ... Got: 'BensOffice' then your LLM replaced the UUID with the human-readable site name. Reinforce: never replace site_id with site_name; if the export has no UUID, keep site_id null and keep site_name.

  4. Pydantic in the repo — The backend defines the import shape in open_fdd/platform/api/data_model.py: DataModelImportBody, PointImportRow, EquipmentImportRow. A script or pipeline can import those models and validate the LLM output (e.g. DataModelImportBody.model_validate(json.loads(llm_output))) before returning it to the human. That way the human only sees JSON that is known to parse on the backend.

Mechanical engineer flow (short)

  1. Create site (and optionally equipment) via API or UI; note site_id.
  2. Export — GET /data-model/export?site_id=YourSiteName (or no filter for full dump).
  3. Upload to LLM — Paste (a) the canonical template above (or your saved copy of the same text), (b) fault/rule context (which faults you run + YAML snippets when possible), then (c) export JSON. Optionally include the import JSON Schema so the LLM returns a valid payload.
    • Fault-first: Answer the pre-flight questions (or let the model ask them) before treating polling as final.
    • UUID reminder: Never replace points[].site_id with a human-readable site name; keep the UUID from the export (see Validate before import below).
  4. Validate — Run schema validation or Pydantic validation on the LLM reply so you know it will parse on the backend.
  5. Import — PUT /data-model/import with the validated JSON.
  6. Run FDD / tests — Trigger an FDD run or Sparkl (or other) tests as needed for the project.