Engineering quantities (EQ-VOCAB)
Open-FDD defines a versioned engineering-quantity vocabulary for design / rated / TAB capacities that feed PyPI ECM tools. Telemetry and FDD math stay in Parquet / DataFusion; these records are model evidence, not historian samples.
| Field | Value |
|---|---|
| Vocab version | ofdd_engineering_quantities_v1 |
| Namespace | urn:openfdd:ns# |
| Turtle | vocab/ofdd_engineering_quantities_v1.ttl |
| JSON schema | vocab/ofdd_engineering_quantities_v1.schema.json |
| Python | open_fdd.ecm_engineering.eq_vocab (wheel copy is authoritative; Pages copy parity-tested) |
Quantity record (required)
Each capacity property points at an EngineeringQuantity record with:
numeric_value(finite) + registeredunit_codequantity_kind(e.g.ElectricalPowervsThermalPower)value_basis(Design|Rated|TAB|Measured|Assumed)source_type/ optional locator +review_status
Do not treat thermal kW as electrical demand. Do not invent annual hours or ton-hours from nameplate alone.
Properties (v1)
ratedCoolingCapacity, ratedHeatingCapacity, ratedFuelInputPower,
ratedElectricalInputPower, ratedShaftPower, designSupplyAirflow,
designOutdoorAirflow, designWaterFlow, designExternalStaticPressure,
designPumpHead, ratedCOP, ratedEER, ratedThermalEfficiency.