Generated parity report

Auto-generated from sql_rules/generated/parity_inventory.yaml. Do not edit by hand. Run python3 scripts/generate_cookbook_report.py.

62 is the executable pandas cookbook (CookbookRule constructors). 66 is the SQL registry: those 62 twins plus 4 SQL-only analytics. Aliases SV-SLEW, FC13, and excess_runtime are not extra rules.

  • Pandas diagnostics: 62
  • SQL analytics: 4
  • SQL registry: 66
  • Building 100 cartesian: 48 equipment × 62 diagnostics

Difference classes

Class Count
alias 2
intentional_non_applicability 4
missing_implementation 1
none 58
semantic_gap 1

Matrix

rule_id title pandas SQL parity class
SV-RANGE Sensor out of hard range _sweep_range sv_range.sql sql_screening none
SV-FLATLINE Sensor flatline (stuck) _sweep_flatline sv_flatline.sql sql_screening none
SV-SPIKE Sensor rate-of-change spike _sweep_spike sv_spike.sql sql_screening none
SV-STALE Stale data (no fresh samples) _sweep_stale sv_stale.sql sql_screening none
SV-RATE Context-aware sensor rate of change _sv_rate_compute sv_rate.sql sql_screening semantic_gap
PID-HUNT-1 Suspected control-output hunting _pid_hunt_1 pid_hunt_1.sql sql_screening none
FC1 Duct static below SP at full fan (GL36 A) fc1 fc1_duct_static_low.sql sql_screening none
FC2 MAT below OAT/RAT envelope (GL36 B) fc2 fc2_mat_low.sql sql_screening none
FC3 MAT above OAT/RAT envelope (GL36 C) fc3 fc3_mat_high.sql sql_screening none
FC4 PID hunting (operating-state oscillation) fc4 fc4_os_hunting.sql sql_screening none
FC5 SAT cold when heating commanded (GL36 D) fc5 fc5_sat_cold_heating.sql sql_screening none
FC6 Estimated OA fraction mismatch fc6 fc6_oa_frac_mismatch.sql sql_screening none
FC7 SAT low with full heating (GL36 E) fc7 fc7_sat_low_heating.sql sql_screening missing_implementation
FC8 SAT/MAT mismatch in economizer (GL36 F) fc8 fc8_sat_mat_econ.sql sql_screening none
FC9 OAT too warm for free cooling (GL36 G) fc9 fc9_oa_sat_sp_econ.sql sql_screening none
FC10 OAT/MAT mismatch + mech cooling (GL36 H) fc10 fc10_mat_oa_clg.sql sql_screening none
FC11 OAT/MAT mismatch economizer-only (GL36 I) fc11 fc11_oa_sat_sp_clg.sql sql_screening none
FC12 SAT above blend in cooling (GL36 J) fc12 fc12_sat_mat_clg.sql sql_screening none
FC13 SAT above SP at full cooling (GL36 K) fc13 sat_high_fault.sql sql_screening alias
FC14 CHW coil ΔT when inactive (GL36 L) fc14 fc14_chw_coil_dt_inactive.sql sql_screening none
FC15 HW coil ΔT when inactive (GL36 M) fc15 fc15_hw_coil_dt_inactive.sql sql_screening none
AHU-SATDEV SAT deviation from setpoint ahu_sat_dev ahu_satdev.sql sql_screening none
AHU-DUCTHI Duct static pressure high ahu_duct_high ahu_ducthi.sql sql_screening none
AHU-SIMUL Heating and cooling simultaneous ahu_simul_heat_cool ahu_simul.sql sql_screening none
OAT-METEO BAS outdoor-air sensor vs Open-Meteo oat_vs_meteo oat_meteo_fault.sql sql_screening none
ECON-1 Economizer stuck closed econ1 econ1_stuck_closed.sql sql_screening none
ECON-2 Economizing when outdoor unfavorable econ2 economizer_fault.sql sql_screening none
ECON-3 Mech cooling without integrated economizer econ2 econ3_mech_without_econ.sql sql_screening none
ECON-4 Low estimated OA fraction econ4 econ4_low_oa_frac.sql sql_screening none
ECON-5 Preheat over-conditioning econ5 econ5_preheat_over.sql sql_screening none
ECON-6 Economizing in freezing weather econ6_compute econ6_econ_freezing.sql sql_screening none
ECON-7 Economizer OK but not economizing econ7_compute econ7_ok_not_economizing.sql sql_screening none
MECH-OAT-1 Mechanical cooling below 60°F web OAT mech_oat1_compute mech_oat_1.sql sql_screening none
CHW-NOLOAD-1 Chiller running with no building load chw_noload1_compute chw_noload_1.sql sql_screening none
VAV-1 Zone comfort band vav1 vav1_comfort_fault.sql sql_screening none
VAV-2 Night setback miss vav2 vav2_night_setback.sql sql_screening none
VAV-3 Excessive reheat during warm weather vav3 vav3_excessive_reheat.sql sql_screening none
VAV-4 Damper stuck at full open vav4 vav4_damper_full_open.sql sql_screening none
VAV-5 Airflow sensor bias vav5 vav5_airflow_bias.sql sql_screening none
VAV-6 Reheat when cooling available vav6 vav6_reheat_free_cool.sql sql_screening none
VAV-REHEAT Reheat valve stuck / no temp rise vav_reheat_stuck vav_reheat.sql sql_screening none
VAV-AHU-LEAVE VAV leave vs parent AHU SAT (fedBy) vav_vs_ahu_leave vav_ahu_leave.sql sql_screening none
VAV-7 Min airflow / fixed high flow vav7 vav7_min_airflow.sql sql_screening none
CHW-1 Low chilled-water ΔT chw1 chw1_low_dt.sql sql_screening none
CHW-2 DP below SP at max pump speed chw2 chw2_dp_low.sql sql_screening none
CHW-3 Plant supply temp outside deadband chw3 chw3_supply_band.sql sql_screening none
CHW-4 Flow high at max pump chw4 chw4_flow_high.sql sql_screening none
HP-1 Discharge cold when heating hp1 hp1_discharge_cold.sql sql_screening none
WX-1 OA temperature spike wx1 wx1_oa_spike.sql sql_screening none
CW-OPT-1 Condenser water not optimized vs wet-bulb cw_opt cw_opt_1.sql sql_screening none
CW-APR-1 High CW approach at full tower fan cw_apr cw_apr_1.sql sql_screening none
CW-FAN-1 Excess tower fan energy vs wet-bulb limit cw_fan_excess cw_fan_1.sql sql_screening none
TRIM-1 Duct static trim advisory trim1 trim1_duct_static.sql sql_screening none
TRIM-3 HWST trim advisory trim3 trim3_hwst.sql sql_screening none
TRIM-4 CHW plant reset advisory trim4 trim4_chw_reset.sql sql_screening none
SCHED-1 Unoccupied runtime sched1 sched1_unoccupied_runtime.sql sql_screening alias
SCHED-247 Always-on fan or pump runtime _sched247 sched247_always_on.sql sql_screening none
RESET-1 SAT reset not tracking outdoor air reset1 reset1_sat_oa_reset.sql sql_screening none
CMD-1 Fan cmd/status mismatch cmd1 cmd1_fan_mismatch.sql sql_screening none
OA-1 Low OA fraction oa1 oa1_low_oa_frac.sql sql_screening none
DMP-1 OA damper leakage dmp1 dmp1_oa_damper_leak.sql sql_screening none
VLV-1 Cooling valve leakage vlv1 vlv1_clg_valve_leak.sql sql_screening none
AVG-ZONE-TEMP Average zone temperature per equipment avg_zone_temp.sql sql_screening intentional_non_applicability
FAN-RUNTIME-HOURS Fan running hours where fan_cmd > 5% (normalized 0-1) fan_runtime_hours.sql sql_screening intentional_non_applicability
FAULT-ELAPSED-HOURS Comfort fault sample count → hours fault_elapsed_hours.sql sql_screening intentional_non_applicability
ZONE-COMFORT-PCT Percent of samples in comfort band zone_comfort_pct.sql sql_screening intentional_non_applicability